How one battery runs the whole house.

Every "whole-home" setup answers the same two questions: where does the battery plug into your house's wiring, and who decides what gets cut when you ask for too much. There are four ways to answer them. They form a ladder, and the cart you're building now sits on rung one.

The idea in 60 seconds

Your breaker panel is a power strip for the house. Duke feeds it from the meter, and every breaker is one circuit: the fridge, the AC, the bathroom outlets.

"Backup" means one thing: when Duke goes dark, a different source feeds some or all of those breakers. That source is your EG4 12000XP plus batteries.

The safety rule that shapes everything: the battery and the grid must never be connected to the same wires at the same time. If they were, your battery would push power back up the street onto a line a lineman thinks is dead. Every option below is just a different device that enforces that rule: a sliding metal plate, a switch inside the inverter, or a computer.

The number that shapes everything else: your 12000XP makes 12,000 W continuous (about 15,000 W for roughly 10 seconds, which is what lets a compressor start). Your house can ask for more than that when the AC, oven, dryer and water heater all run together. So "whole home" always comes with "and something manages the big stuff."

The four rungs

Cheapest and most hands-on at the top. Most automatic and most expensive at the bottom. Tap + on each one for the details.

1Now · the cart you're building

Extension cords

The cart has outlets. You run cords to the fridge, router and fans. Nothing touches the house wiring.

Cost$0 extra
Whole house?No
Switch-overYou, by hand

Zero permits and zero risk to the house. You learn the inverter's screen, how fast 10 kWh runs out, and which appliances actually matter. That knowledge decides how far up this ladder you need to climb.

2The cheap whole-home trick

Inlet + interlock

An electrician puts a power inlet (a male plug socket) on the outside wall and an interlock kit on your main panel. To use it, you plug the cart into the inlet with one heavy cord, slide the plate, and flip the breaker. Your whole panel is now fed by the cart.

Cost~$500–1,000 installed*
Whole house?Yes, if you manage it
Switch-overYou, ~2 min

The interlock is a sliding metal plate. Your main breaker (from Duke) and the new "backfeed" breaker (from the inlet) sit next to each other, and the plate makes it physically impossible to have both on. It's the same setup people use for portable generators, so electricians and inspectors already know it well.

You are the load manager. Before you flip over, you turn off the water heater, dryer and oven breakers, and keep the AC to one unit. Forget, and the inverter trips. That doesn't hurt anything, but it's annoying.

Size: a 50 A, 240 V inlet matches the 12000XP's output (12 kW ÷ 240 V = 50 A). The heavy cord is a 50 A generator cord.

Why this fits you

It works with the cart. The battery stays in the shed, rolls to the wall when a storm's coming, and your whole panel lights up. It's the "middle ground" you asked for.

3The classic "smart switch thing"

Critical-loads subpanel

A second, smaller breaker box next to your main one. You move your must-have circuits into it (fridge, mini-split, lights, router, a few outlets). The inverter sits permanently between the main panel and that subpanel.

Cost~$1,500–3,000 installed*
Whole house?No, chosen circuits
Switch-overAutomatic, <10 ms

The 12000XP has the transfer switch built in. When Duke drops, it opens its grid relay and feeds the subpanel from the battery in under 10 milliseconds. Clocks don't reset, and the Wi-Fi doesn't blink. You don't buy a separate automatic transfer switch.

Overload is impossible by design, because the big loads were never moved over. That's why this is the one most installers pick.

The catch for you: the inverter has to be permanently wired next to the house panel. That doesn't fit a cart that lives in the shed. It fits the 32 kWh "build it in place" version.

4True whole-home

Inverter in front of the main panel

The inverter sits between the meter and your entire main panel. Duke's power passes through it on a normal day. In an outage the battery feeds every breaker in the house, automatically.

Cost~$2,500–5,000 installed*
Whole house?Yes, automatic
Switch-overAutomatic, <10 ms

Everything the house uses on a normal day has to pass through the inverter, and the 12000XP's pass-through limit is 100 A (EG4 spec sheet). If your panel is 150 A or 200 A, the electrician has to do a load calculation to show your house really peaks under 100 A, then put a 100 A breaker in a new disconnect at the meter. A 1,300 sq ft house with a heat pump and a mini-split often passes. An electric range, dryer and water heater all in the same house make it tighter. Only the calculation can tell.

Overload in an outage: the battery side is still 12 kW. Something has to drop the big stuff. That's the job of the smart load port, which is built in and free, or a smart panel, which costs money. See next section.

This is the version EG4 means when it says the 12000XP "provides true whole-home backup." The wiring diagrams are in EG4's 12000XP System Wiring Diagrams PDF (link below).

* Installed costs are my estimates for St. Pete licensed-electrician work, not quotes. Rungs 2–4 all touch the house panel, so all three need a permit and a licensed electrician to make the final connection.

So what's a "smart panel"?

It's not a way to connect the battery. Rungs 2–4 already do that. It's a brain that sits on top of rung 4 and turns individual circuits off and on so a 12 kW inverter can run a house that sometimes wants 20 kW.

OptionWhat it doesFor your 12000XP
Smart load port
built into the 12000XP
One output that switches off automatically when the battery gets low or there's no sun. You wire the water heater or the dryer to it.Free, use it first. Handles one big load.
Lumin Smart PanelA box next to your panel that controls up to ~14 circuits from an app, with rules like "in an outage, drop the dryer and the oven." EG4 has announced an integration with it.Works as a standalone circuit controller. ~$2,500 for the panel alone (2024 price) plus install.
EG4 GridBOSSEG4's own 200 A smart gateway for whole-home and generator management.Not compatible. EG4 lists only the 12kPV / 18kPV / FlexBOSS inverters. Skip it.
SPAN panelReplaces your whole breaker panel with an app-controlled one.Built around partner battery systems. I couldn't confirm it works with the 12000XP. Not a starting point.
The plain version

A smart panel is an automatic version of the interlock habit on rung 2, where you walk to the panel and turn off the dryer and water heater before you flip over. It does it for you, per circuit, in milliseconds. That's worth paying for once you're on rung 4. On rungs 1–3 you don't need one.

Try it: the outage simulator

Duke just went dark. Pick a rung, then tap appliances on. The line marks the 12000XP's 12 kW limit. Wattages are typical running watts, and your actual units will differ.

My pick for you

Climb to rung 2 and stop there for a while. Build the cart this winter, then pay an electrician for an inlet + interlock before next hurricane season. That gets you whole-panel backup for about $500–1,000 on top of the cart, it fits the "battery lives in the shed" plan, and it teaches you load management with your own hands. That's the exact skill that tells you later whether rung 4 is worth $2,500–5,000.

Go to rung 4 later, when the battery is big enough to matter (20–30 kWh), it has a permanent home, and you're tired of walking to the panel. At that point, use the 12000XP's free smart load port for the water heater first and add Lumin only if you still trip.

Skip rung 3 unless you decide the battery should live permanently against the house. It's the right answer for a fixed install, but it doesn't fit a cart.

Before rung 2 or 4

Ask the electrician for a load calculation and your panel's amp rating (it's printed on the main breaker). Also ask whether your panel brand has a listed interlock kit. Older panels sometimes don't, and that's the one thing that can push rung 2 into a panel swap.

Say this to the electrician (rung 2)

"I want a 50-amp, 240-volt generator inlet on the outside wall, a listed interlock kit for my main panel, and a 2-pole 50 A backfeed breaker, permitted. The source will be an EG4 12000XP inverter on a cart, so it's a separately derived system question. Tell me how you want neutral and ground handled at the inlet."

Your house already bonds neutral to ground at the main panel. An inverter can bond them too. If both do it, ground wires carry current they shouldn't. The 12000XP has a setting for this. The electrician needs to know it's an inverter and not a generator so they can tell you how to set it. It's the most common mistake on interlock + inverter setups, and asking about it marks you as someone who did the homework.

Learn more (real sources)

In the order I'd read them.

1 · Your inverter's own mapEG4 12000XP System Wiring Diagrams (PDF)Official drawings for critical-loads, whole-home and generator setups on your inverter. Big file, so open it on Wi-Fi. 2 · The specsEG4 12000XP product page + spec sheet100 A pass-through, 12 kW out, 15.36 kW for about 10 seconds, smart load port. These are the numbers everything above comes from. 3 · Will Prowse12kW Budget Whole-Home SystemWill's page on tying a 12000XP-class system to the house: transfer switch vs critical-loads subpanel vs meter collar. 4 · Saves you $EG4 forum: why the 12000XP isn't GridBOSS-compatibleRead it before anyone tries to sell you one. 5 · The smart panelEnergySage: Lumin Smart Panel reviewWhat it controls, what it costs, and the "small company" caveat. 6 · Watch itYouTube: generator interlock kit, how it worksRung 2 explained by electricians. The generator version is identical, just swap "generator" for "your cart."

Quiz: four questions

If you can answer these, you can hold your own with an electrician.